Specifications
Features
75W Single Output Industrial DIN Rail Power Supply NDR-75 series Universal AC input / Full range Protections: Short circuit / Overload / Over voltage/ Over temperature Cooling by free air convection Can be installed on DlN rail TS-35/7.5 or 15 UL 508 (industrial control equipment} approved EN61000-6-2(EN50082-2} industrial immunity level 100% full load burn-in test 3 years warrantyMODEL | NDR-75-12 | NDR-75-24 | NDR-75-48 |
DC VOLTAGE | 12V | 24V | 48V |
RATED CURRENT | 6.3A | 3.2A | 1.6A |
CURRENT RANGE | 0 ~ 6.3A | 0 ~ 3.2A | 0 ~ 1.6A |
RATED POWER | 75.6W | 76.8W | 76.8W |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 150mVp-p |
VOLTAGE ADJ. RANGE | 12 ~ 14V | 24 ~ 28V | 48 ~ 55V |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% |
SETUP, RISE TIME | 1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load | ||
HOLD UP TIME (Typ.) | 60ms/230VAC 12ms/115VAC at full load | ||
VOLTAGE RANGE Note.6 | 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] | ||
FREQUENCY RANGE | 47 ~ 63Hz | ||
EFFICIENCY (Typ.) | 85.50% | 88% | 89% |
AC CURRENT (Typ.) | 1.45A/115VAC 0.9A/230VAC | ||
INRUSH CURRENT (Typ.) | 20A/115VAC 35A/230VAC | ||
LEAKAGE CURRENT | <1mA / 240VAC | ||
OVERLOAD | 105 ~ 130% rated output power | ||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | |||
OVER VOLTAGE | 14 ~ 17V | 29 ~ 33V | 56 ~ 65V |
Protection type : Shut down o/p voltage, re-power on to recover | |||
OVER TEMPERATURE | Protection type : Shut down o/p voltage, re-power on to recover | ||
WORKING TEMP. | -20 ~ +70℃ (Refer to "Derating Curve") | ||
WORKING HUMIDITY | 20 ~ 95% RH non-condensing | ||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | ||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | ||
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | ||
SAFETY STANDARDS | UL508, TUV EN62368-1, EAC TP TC 004 approved;(meet EN60204-1) | ||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | ||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | ||
EMC EMISSION | Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020 | ||
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A, EAC TP TC 020 | ||
MTBF | 486.2K hrs min. MIL-HDBK-217F (25℃) | ||
DIMENSION | 32*125.2*102mm (W*H*D) | ||
PACKING | 0.51Kg; 28pcs/15.3Kg/1.22CUFT | ||
NOTE |
| ||
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |