Single Output power supply with UPS(Uninterrupted) function. This type of power supply can function as usual in emergency situations such as power outages. It can provide a continuous, stable, uninterrupted power supply.The principle is relatively complex, the input and output are AC AC-AC (including AC-DC, DC-DC, DC-AC).The function focuses on keeping the output power supply stable, at the same time to ensure that the input is abnormal can still continue to uninterrupted power supply, with high reliability and high anti-interference. We have designed LED director to show the power ON/OFF and all kinds of protections,you can rest assured when use it.You can use this kind of products in many situations when you need battery charge. We also provide 2 years warranty,this is our guarantee for product quality.We promise to provide our technical support wholeheartedly.You can always trust a mature technical team. LEYU electric products,your cost-effective choice.
Features
UPS power function function
Introduction and use of UPS power supply
UPS power supply refers to uninterruptible power supply, which is a system equipment that connects the battery to the host and converts DC power into mains power through the host inverter and other module circuits. It is mainly used to provide a stable and uninterrupted power supply to a single computer, computer network system or other power electronic equipment such as solenoid valves, pressure transmitters, etc. When the mains input is normal, the UPS will stabilize the mains and supply it to the load. At this time, the UPS is an AC-type voltage stabilizer, and it also charges the battery in the machine; when the mains is interrupted (accidental power failure) Immediately, the UPS will continue to supply 220V AC power to the load by switching and converting the DC power from the battery to the load, so that the load can maintain normal operation and protect the software and hardware of the load from damage.Specifications
SPECIFICATION | ||||
AD-55A | AD-55B | |||
MODEL | ||||
OUTPUT | CH1 | CH2 | CH1 | CH2 |
Output number | 13.8V | 13.4V | 27.6V(24V) | 26.5V(24V) |
DC voltage | 3.5A | 0.23A | 1.8A | 0.16A |
Rated Current | 0~4A | -------- | 0~2A | -------- |
Current Range | 51.38W | 53.92W | ||
Rated Power | 100mVp-p | -------- | 100mVp-p | -------- |
Ripple & Noise | CH1:12~14.5V | CH1:24~29V | ||
Voltage Adj. Range | ±1.0% | -------- | ±1.0% | -------- |
Voltage Tolerance | ±0.5% | -------- | ±0.5% | -------- |
Line Regulation | ±0.5% | -------- | ±0.5% | -------- |
Load Regulation | 800ms,50ms/230VAC 1600ms,50ms/115VAC at full load | |||
Setup, Rise Time | 80ms/230VAC 16ms/115VAC at full load | |||
INPUT | ||||
Voltage Range | 88~264VAC 47~63Hz; 124~370VDC | |||
AC Current | 1.6A/115VAC 1A/230VAC | |||
Efficiency | 71% | 74% | ||
Inrush Current | Cold start 20A/115VAC 40A/230VAC | |||
Leakage Current | <1mA /240VAC | |||
PROTECTION | ||||
Over Load | 105~150% rated output power | |||
Protection type: AC Charging Mode: Hiccup mode, recovers automatically after fault condition is removed UPS Mode: Protected by internal fuse | ||||
Over Voltage | CH1:15.87~18.63V | CH1:31.74~37.26V | ||
Protection type: Hiccup mode,recovers automatically after fault condition is removed | ||||
Battery Low | 9.5~11V | 20~22V | ||
ENVIRONMENT | ||||
Working Temp. | -10~+60℃ (Refer to “Derating Curve”) | |||
Working Humidity | 20~90%RH non-condensing | |||
Storage Temp., Humidity | -20~+85℃,10~95%RH | |||
Temp. Coefficient | ±0.03%/ ℃(0~50℃ )on CH1 output | |||
Vibration | 10~500Hz,2G10min./1cycle,60min.each along X, Y,Z axes | |||
SAFETY &EMC | ||||
Safety Standards | UL60950-1, TUV EN60950-1 approved | |||
Withstand Voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |||
Isolation Resistance | I/P-O/P,I/P-FG,O/P-FG:100M Ohms/500VDC /25℃ /70%RH | |||
EMC Emission | Compliance to EN55022(CISPR22) Class B, EN61000-3-2,-3 | |||
EMC Immunity | Compliance to EN61000-4-2,3,4,5,6,8,11,EN55024,light industry level, criteria A | |||
OTHERS | ||||
Dimension | 159*97*38mm(L*W*H) | |||
Weight | 0.5Kg | |||
Packing | 24pcs/12.60Kg/0.75CUFT | |||
NOTE | ||||
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. | ||||
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. | ||||
3. Tolerance: includes set up tolerance, line regulation and load regulation. | ||||
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |