Features
Proper use of guide rail power supply
Specifications
SPECIFICATIONS | ||||
OUTPUT | ||||
Model | DR-45-5 | DR-45-12 | DR-45-15 | DR-45-24 |
DC Voltage | 5V | 12V | 15V | 24V |
Rated Current | 5A | 3.5A | 2.8A | 2A |
Current Range | 0-5A | 0-3.5A | 0-2.8A | 0-2A |
Rated Power | 25W | 42W | 42W | 48W |
Ripple & Noise | 100mVp-p | 200mVp-p | 240mVp-p | 480mVp-p |
Voltage Adj. Range | 4.75-5.5V | 10.8-13.2V | 13.5-16.5V | 21.6-26.4V |
Voltage Tolerance | ±2% | ±1% | ±1% | ±1% |
Line regulation | ±1% | ±1% | ±1% | ±1% |
Load regulation | ±1% | ±1% | ±1% | ±1% |
Setup, Rise, Hold Up Time | 800ms, 60ms/230VAC at full load 60ms/230VAC at full load | |||
INPUT | ||||
Voltage Range | 85~264VAC 47~63Hz; 120~370VDC | |||
AC Current | 1.5A/115V 0.75A/230V | |||
Efficiency | 72% | 77% | 77% | 80% |
Inrush Current | Cold start 28A/115VAC 56A/230VAC | |||
Leakage Current | <1mA/240VAC | |||
PROTECTION | ||||
Over Load | 105%~150% rated output power | |||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||||
Over Voltage | 5.75-6.75VAC | 13.8-16.2VAC | 17.25-20.25VAC | 27.6-32.4VAC |
Protection type: Shut off o/p voltage, clamping by zener diode | ||||
Over Temp.. | Tj 135℃ typically (U1) Detect on heat sink of power transistor | |||
Protection type: Shut down o/p voltage, re-power on to recover | ||||
ENVIRONMENT | ||||
Working Temp., Humidity | -10℃~+50℃; 20%~90%RH non-condensing | |||
Storage Temp., Humidity | -20℃~+85℃; 10%~95%RH | |||
Temp. Coefficient | ±0.03%/℃(0~50℃) | |||
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||
SAFETY | ||||
Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC | |||
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC/20℃/70%RH | |||
STANDARD | ||||
Safety Standard | Design refer to UL508,TUV EN60950-1 | |||
EMC Standard | Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2(EN50082-2),heavy industry level, criteria A | |||
OTHERS | ||||
Dimension | 93*78*67mm (L*W*H) | |||
Weight | 0.31Kg | |||
Packing | 48pcs/17.5Kg/1.3CUFT | |||
NOTE | ||||
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1μ & 47μ parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |