1, switching power supply metal shell power supply shell is generally connected with the ground (FG), to be reliably grounded, to ensure safety, can not be mistakenly connected to the shell on the zero line;2. Before the installation of switching power supply is completed and powered for trial use, please check and proofread the connection on the terminals again, and make sure that the input and output, AC and DC, single-phase and multi-phase, positive and negative, voltage and current values are correct, and can be powered on.3, for high-power switching power supply, there are generally two or more than two "+" output terminals "-" "output terminals, in fact, they belong to an output electrode, just for the convenience of users wiring, and the multiple terminals respectively in the internal and connected together;4. In order to achieve full heat dissipation, the general switching power supply should be installed in the position of better air convection conditions, or installed on the chassis shell through the shell to transmit the heat outdoors;5. Switching power supply is tested with resistive load before delivery. If it needs to be used in capacitive or inductive load, it should be explained in the order contract in advance.6, for double switching power supply output symmetrical load, the preferred symmetric output power supply;7. For users with grounded switching power supply FG, it is a normal phenomenon to touch the shell or have hemp electric feeling in the output. When floating to the ground, FG has about 110V AC output to the ground, which is determined by the internal structure of the power supply.8, switching power supply in the factory before 100% full negative aging, the power utilization rate is generally controlled within 80% or lower, can greatly improve the service life of the power supply, the general situation of power supply temperature increases 10℃ capacitor life reduced - half;9, switching power supply ripple and noise is superposed on the DC output voltage of AC components, generally expressed with millivolt peak;10, for all switching power supply, when the load mutation, there will be a certain response time, during this mutation, the output voltage of the power supply in the instantaneous will have a short overshoot process, and then return to the normal output state, this is the dynamic response;11, once the switch power supply failure, should notify the factory in the fastest way, the factory will be responsible for free maintenance or technical guidance, except for the private dismantling of the power supply.200W Single Output Switching Power Supply LRS-200 seriesAC input range selectable by switchWithstand 300VAC surge input for 5 secondProtections: Short circuit / Overload / Over voltage/ Over temperatureCooling by free air convectionLED indicator for power on100% full load burn-in testHigh operating temperature up to 70℃High efficiency, long life and high reliability2 years warranty
Features
Notes for switching power supply
Specifications
SPECIFICATION
OUTPUT
Model
LRS-200-3.3
LRS-200-5
LRS-200-12
LRS-200-15
LRS-200-24
LRS-200-36
LRS-200-48
DC Voltage
3.3V
5V
12V
15V
24V
36V
48V
Rated Current
40A
40A
17A
14A
8.8A
5.9A
4.4A
Current Range
0~40A
0~40A
0~17A
0~14A
0~8.8A
0~5.9A
0~4.4A
Rated Power
132W
200W
204W
210W
211.2W
212.4W
211.2W
Ripple & Noise
150mVp-p
150mVp-p
150mVp-p
150mVp-p
150mVp-p
200mVp-p
200mVp-p
Voltage Adj. Range
2.97~3.6V
4.5 ~ 5.5V
10.2~ 13.8V
13.5~18V
21.6~28.8V
32.4~39.6V
43.2~52.8V
Voltage Tolerance
±3.0%
±3.0%
±1.5%
±1.0%
±1.0%
±1.0%
±1.0%
Line Regulation
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
Load Regulation
±2.5%
±2.0%
±1.0%
±0.5%
±0.5%
±0.5%
±0.5%
Setup, Rise Time
1300ms, 50ms/230VAC 1300ms, 50ms/115VAC at full load
Hold Up Time
16ms/230VAC 12ms/115VAC at full load
INPUT
Voltage Range
90 ~ 132VAC / 180 ~ 264VAC selected by switch 254 ~ 370VDC (switch on 230VAC)
Frequency Range
47 ~ 63Hz
Efficiency
87%
88%
89.50%
89.50%
90%
AC Current
4A/115VAC 2.2A/230VAC
Inrush Current
Cold start 60A/115VAC 60A/230VAC
Leakage Current
<2mA / 240VAC
PROTECTION
Over Load
110 ~ 140% rated output power
Protection type: Hiccup mode, recovers automatically after fault condition is removed
Over Voltage
5.75~6.75V
13.8 ~ 16.2V
18~21V
28.8 ~ 33.6V
41.4~46.8V
55.2~ 64.8V
Protection type: Hiccup mode, recovers automatically after fault condition is removed
Over temperature
Hiccup mode, recovers automatically after fault condition is removed
ENVIRONMENT
Working Temp.
-25 ~ +70℃ (Refer to “derating curve”)
Working Humidity
20 ~ 90% RH non-condensing
Storage Temp., Humidity
-40 ~ +85℃, 10 ~ 95% RH
Temp. Coefficient
±0.03%/℃ (0 ~ 50℃)
Vibration
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance: includes set up tolerance, line regulation and load regulation. 4. Line regulation is measured from low line to high line at rated load. 5. Load regulation is measured from 0% to 100% rated load. 6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 7. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.