Specifications
Features
120W Single Output Industrial DIN Rail Power Supply NDR-120 series Universal AC input / Full range EMC standards: EN55022 class B Economical and slim design Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Can be installed on DIN rail TS-35 / 7.5 or 15 EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test 2 years warranty MODEL | NDR-120-12 | NDR-120-24 | NDR-120-48 | |
OUTPUT | DCVOLTAGE | 12V | 24V | 48V |
RATEDCURRENT | 10A | 5A | 2.5A | |
CURRENTRANGE | 0 ~ 10A | 0 ~ 5A | 0 ~ 2.5A | |
RATEDPOWER | 120W | 120W | 120W | |
RIPPLE&NOISENOTE.2 | 100mVp-p | 120MVP-P | 150MVP-P | |
VOLTAGEADJ.RANGE | 12 ~ 14V | 24 ~ 28V | 48 ~ 55V | |
VOLTAGETOLERANCE | 2.0% | 1.0% | 1.0% | |
LINEREGULATION | 0.5% | 0.5% | 0.5% | |
LOADREGULATION | 1.0% | 1.0% | 1.0% | |
SETUP.RISE TIME | 1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load | |||
INPUT | VOLTAGERANGE | 90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)] | ||
FREQUENCYRANGE | 47~63HZ | |||
EFFICIENCY | 85.5% | 88% | 89% | |
AC CURRENT | 2.25A/115VAC 1.3A/230VAC | |||
INRUSH CURRENT | 20A/115VAC 35A/230VAC | |||
LEAKAGECURRENT | <1mA / 240VAC | |||
PROTECTION | OVERLOAD | 105 ~ 130% rated output power Protection type: Constant current limiting, recovers automatically after fault condition is removed. | ||
OVER VOLTAG | 14 ~ 17V | 29 ~ 33V | 56 ~ 65V | |
Protection type: Shut down o/p voltage, re-power on to recover. | ||||
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover. | |||
Others | Packing | 0.6Kg; 20pcs/13Kg/1.16CUFT | ||
Dimention | 40*125.2*113.5mm (W*H*D) |